top of page

Features

 

  • 45mm for 32A, 55mm for 63A and 70mm for 100A
  • Three position operator: ON-OFF-TRIP
  • Complete range of common accessories
  • Handle lock in the OFF position
  • Class 10 overload trip characteristics
  • Trip test available
  • Finger safe terminal
  • FDIN rail & Screw mounting

 

 

Characteristics

 

General

Meta-MEC MMSs are suitable for switching and protecting three-phase induction motors of up to 45kW at 400VAC and for loads with rated currents of up to 100A.

 

Types

- MMS32S, MMS32H, MMS63S, MMS63H, MMS100S, MMS100H

 

Rating

- It covers all ratings up to 100A




 

Function

  • Protection of group installation
  • Protection of circuits
  • Motor protection & Starter protection
  • Wide range of ambient temperature compensation
  • Phase failure protection

 

Standard

The components fulfill the international standard IEC 60947.

In U.S, the devices can be used as Manual Motor Starter in Group Installations according UL508. The approval for UL508 Type E Combination Starter is under preparation.

 

Design concept for user’s efficiency

Dial cover for current setting, cover lock device, large scale letter

Identification label

Handle lock function in OFF position & Three position handle

Trip test device

Insulation barrier

 

Mounting & Connection

Terminals

35mm/75mm din-rail standard mounting & screw mounting

Finger safe terminal cover

Direct adapter (Connection kit with mini Magnetic Contactor)

 

Accessories

Front mounting auxiliary switch

Side mounting auxiliary switch

Side mounting alarm switch

Side mounting shunt release

Side mounting undervoltage release

Side mounting undervoltage release with 2NO switch)

 

 

Ratings

 

Function - Motor protection (Trip class 10)

  • Short circuit
  • Over-current
  • Phase failure
  • Adjustable thermal release
  • Ambient temperature compensation

 

Ratings

  • Ampere Frame : 32, 63, 100AF
  • Rated operating voltage (Ue) : 1000V (690V for MMS-32)
  • Rated frequency (Hz) : 50/60Hz
  • Rated insulation voltage (Uimp) : 8kV (6kV for MMS-32)
  • Utilization category : Cat A., AC3
  • Instantaneous short circuit : 13 x Ie max
  • Wide operation temperature : -20 ~ +60

MMS-63S

$339.04Price
    bottom of page